What is the function of a fire alarm control panel?

November 15, 2026 by
What is the function of a fire alarm control panel?
CÔNG TY CỔ PHẦN ĐẦU TƯ THƯƠNG MẠI DỊCH VỤ VÀ TƯ VẤN ĐỖ LÊ VŨ, Marketing Team - SAMASER Holdings

The fire alarm control panel (fire alarm control cabinet) determines whether the fire detection system reports correctly, promptly, and accurately. So what is the function of the fire alarm control panel, how to install it according to standards, and which type to choose for the project? This article answers each question in turn.

What is a fire alarm control panel?

A fire alarm control panel is the control and display device of the fire alarm system. According to the definition in Article 3.6 TCVN 5738:2021, this is the device that supplies power to automatic fire detectors and other devices in the system, while receiving, processing signals, and issuing alarm commands.

In the European standard set, this device is called control and indicating equipment and certified according to EN 54-2. In Vietnam, the corresponding standard is TCVN 7568-2:2013 (ISO 7240-2).

What are the main functions of the fire alarm center?

The fire alarm center has 6 main functions: supplying power to devices, receiving and checking signals, issuing alarms and indicating fire locations, monitoring incidents, transmitting signals over long distances, and controlling interlocking devices. These functions are stated in Article 3.6 and Article 5 TCVN 5738:2021.

No.

Function

Content

1

Power supply

Powering detectors, push buttons, modules on the signal circuit

2

Receiving and checking signals

Automatically checking signals from detectors and other devices to eliminate false alarms (Article 5.1)

3

Alarm and location indication

Sounding alarms, lights, and indicating the zone or fire address

4

Incident monitoring

Detecting wire breaks, short circuits, power faults; incident signals other than fire signals (Article 5.9)

5

Signal transmission

Transmitting signals to the receiving location or automatic fire extinguishing system

6

Interlocking control

Issuing commands to bells, sirens, smoke exhaust fans, elevators, cutting power, fire extinguishing systems

TCVN 5738:2021 also does not allow the use of devices without fire alarm functions as fire alarm centers, and requires the center to be compatible with the connected detectors.

How do conventional and addressable fire alarm centers differ?

Conventional fire alarm centers report locations by zone, suitable for small and medium-sized buildings. Addressable fire alarm centers identify each device on the loop, providing more detailed displays and more flexible interlocking programming. For example, with Finder's panels:

Information

Finder FF-CF104 / FF-CF108 (conventional)

Finder FF-SYN2L (addressable)

Finder FF-FCP500 (addressable)

Capacity

4 zones / 8 zones, maximum total of 80 / 160 detectors

2 loops

1–4 loops, 255 addresses per loop

Display

Keys and LED status lights for each zone

260 × 64 pixel graphic LCD screen; options for 16, 48, or 96 zone lights

7-inch color LCD screen, 48 LED lights

Output

1 output for 24 V DC 0.5 A siren; fire relay and fault relay 24 V 1 A

2 programmable siren outputs

5 outputs

Other features

Alarm verification, day/night mode, 3 levels of operation

Network connection for up to 64 panels/repeaters

Store 1,000 events, built-in printer; RS232, RS485, CAN, USB

Certification

100 Series certified to EN 54

4 A power supply according to EN 54-4

EN 54-2, EN 54-4, LPCB

For more on how to read zones and loops, see the article [zones and loops in fire alarm systems](zone-va-loop-trong-he-thong-bao-chay-khac-nhau-the-nao).

What requirements must be followed when installing a fire alarm control panel?

TCVN 5738:2021 clearly specifies the location, height, and distance when installing the cabinet. The most important point: the cabinet must be placed where there are personnel on duty 24/7; otherwise, fire alarm signals and incidents must be transferred to a location with personnel on duty and measures must be taken to prevent unauthorized access.

Requirements

Value

Condition

Location

A place with personnel on duty 24/7, with no fire or explosion risk

5.2, 5.3

Height of the control part

0.8–1.8 m from the floor (when installed on walls, columns, racks)

5.7

Installed on a flammable surface

A thick metal sheet of at least 1 mm or non-flammable material of at least 10 mm, wider than each side of the cabinet by 100 mm

5.4

Distance from flammable ceiling

At least 1.0 m

5.5

Distance from adjacent cabinet

At least 50 mm

5.6

Channel reserve (regular cabinet)

At least 10%

5.11

Power supply and grounding

2 independent power sources; the cabinet must be grounded for protection

10.1, 10.2

The temperature and humidity where the cabinet is placed must comply with the manufacturer's specifications. For example, the Finder FF-CF104/CF108 cabinet operates at -5 to 40 °C, with 93% RH, and an IP40 protection rating. Power requirements are explained in the article [main power source and backup power source of the fire alarm cabinet](nguon-chinh-va-nguon-du-phong-cua-tu-bao-chay-co-vai-tro-gi).

What should be compared when selecting a fire alarm control panel?

When selecting a fire alarm control panel, it is necessary to compare the cabinet's capacity with the number of devices in the project, the interconnectivity capability, and compatibility with existing equipment. Choosing the right cabinet from the start helps avoid having to replace it when the project expands.

  • Zone number or loop number, plus a reserve for expansion.

  • Number of output sirens, relays, and interlocking modules needed.

  • Compatible input devices: the address panel, detectors, and modules must share the same protocol with the panel.

  • Need for networking multiple panels, repeater boards, remote monitoring, or BMS integration.

  • Certification of the correct panel model (e.g., EN 54-2, EN 54-4) and documentation required by the investor.

Frequently Asked Questions

Does the fire alarm panel need to be placed in the control room? According to TCVN 5738:2021, the panel must be placed where someone is on duty 24/7. If not, the signal must be transferred to a location with personnel on duty.

Can the fire alarm panel autonomously control the fire suppression system? Yes, if the panel has suitable outputs or modules. In that case, each point requires 2 detectors belonging to 2 channels or 2 different addresses according to TCVN 5738:2021.

Can the fire alarm panel be replaced while keeping the old detectors? It is generally more feasible with conventional systems; with addressable systems, it depends on the manufacturer's protocol. Compatibility documentation should be checked before making a decision.

Finder fire alarm panel at Handyman

Handyman provides Finder fire alarm panels of the conventional series (FF-CF104, FF-CF108) and addressable series (200, 500, 700 Series). DLV Corporation (Handyman) is an authorized installer for the Finder fire alarm system, providing technical support to select the right panel according to the scale of the project and supplying complete contracts, VAT invoices, and documentation as required by the industry.

View and request a quote in the fire alarm panel catalog or call the hotline 0988.678.120.