Fire alarm system: structure, classification, and selection information

November 14, 2026 by
Fire alarm system: structure, classification, and selection information
CÔNG TY CỔ PHẦN ĐẦU TƯ THƯƠNG MẠI DỊCH VỤ VÀ TƯ VẤN ĐỖ LÊ VŨ, Marketing Team - SAMASER Holdings

The fire alarm system is the first layer of protection for factories, warehouses, buildings, and industrial facilities: early detection, accurate location reporting, and activation of response measures. This article summarizes the structure, types of systems, main requirements according to Vietnamese standards, and the information you need to prepare before making a selection.

What is a fire alarm system?

An automatic fire alarm system is a collection of devices that detect signs of fire (smoke, heat, flames), transmit signals to a central unit, issue alerts through sound and light, and indicate the area where the incident occurs. The system operates continuously 24/7 and can interconnect with fire suppression, ventilation, and elevator systems.

In Vietnam, the minimum technical requirements for this system are specified in TCVN 5738:2021 Fire Prevention and Fighting – Automatic Fire Alarm System – Technical Requirements, replacing TCVN 5738:2001. The standard is applied in conjunction with the TCVN 7568 (ISO 7240) series on fire alarm systems.

 What components does a fire alarm system consist of?

A fire alarm system consists of 5 basic component groups: fire alarm control panel, fire detectors, manual call points, linking components, and power supply. Each group is responsible for a step in the detection – processing – alerting chain, so missing or incorrectly selecting one group will affect the entire system.

Component

Role

Example devices

Fire alarm control panel

Supplies power to detectors, receives and processes signals, triggers alarms, monitors line faults

Conventional fire alarm panel, addressable fire alarm panel

Fire detector

Automatically detects smoke, heat, or flames

Smoke detector, heat detector, flame detector, beam smoke detector

Manual call point

A person detecting a fire manually activates the alarm

Conventional call point, addressable call point

Linking components

Connects and transmits signals between devices, controls peripheral devices

Signal cables, input/output modules, isolator modules, bells, sirens, lights

Power supply

Maintains operation when there is mains power and during power outages

Power supply in the panel, backup power supply, emergency battery

How the components coordinate with each other is detailed in the article [structure and principle of the fire alarm system](need URL for article 2).

What types of fire alarm systems are there?

The most common classification is based on how the center identifies the fire location: conventional fire alarm systems (by zone) and addressable fire alarm systems (by individual device). Additionally, there are wireless systems and specialized lines for maritime use and hazardous fire and explosion areas.

Criteria

Conventional fire alarm

Addressable fire alarm

Location reporting method

By zone (channel): knows the area, does not know which detector

By address: knows the exact alarm device

Wired

Each zone has a separate circuit

Multiple devices share one loop

Suitable

Small and medium-sized buildings, few rooms

Large buildings, many areas, need interconnection of multiple systems

For example, Finder

FF-CF104 panel (4 zones), FF-CF108 panel (8 zones)

FF-SYN2L panel (2 loops), FF-FCP500 panel (1–4 loops)

With conventional systems, TCVN 5738:2021 limits the area of each channel to no more than 2,000 m² for open areas and 500 m² for closed areas. The difference between zone and loop is explained in the article [zone and loop in fire alarm systems](need URL article 4).

What standards apply to fire alarm systems in Vietnam?

TCVN 5738:2021 is the main standard for the technical requirements of automatic fire alarm systems, applied along with the TCVN 7568 set (ISO 7240). For imported devices, customers often encounter the European standard EN 54, where each part specifies a type of device.

Some notable requirements in TCVN 5738:2021:

  • The fire alarm center must be located where there is personnel on duty 24/7; otherwise, fire and incident signals must be transferred to a location with personnel on duty (Clause 5.2).

  • The conventional fire alarm center needs to reserve at least 10% of the channels (Clause 5.11).

  • The system uses two independent power sources: 220 V AC mains and a backup battery (Clause 10.1).

Standard EN 54

Device

EN 54-2

Fire alarm control panel (control and display device)

EN 54-4

Power supply device

EN 54-17

Short circuit isolator

What information should be prepared when selecting a fire alarm system?

Before requesting a quote, you should prepare information about the project, installation environment, and existing system. This information determines the type of panel (conventional or addressable), number of zones or loops, type of detectors, and backup power capacity.

  • Scale: area, number of floors, number of rooms or areas to be protected.

  • Environment: dust, humidity, high temperature, areas at risk of fire or explosion, on ships or offshore structures.

  • Interlinked: automatic fire extinguishing system, smoke extraction fans, elevators, power cut, evacuation sound.

  • Old system (if replacing): brand, panel model, number of zones/loops, wiring diagram, type of cable in use.

  • Documentation: fire protection design drawings, investor's documentation requirements.

Frequently asked questions

Does the fire alarm system need to operate continuously? 

Yes. According to TCVN 5738:2021, the system must operate 24/7 and have a backup power source in case of mains failure.

Should I choose a conventional or addressable fire alarm? 

For small projects with few areas, a conventional system is usually used. For large projects with many rooms or where precise alarm device identification is needed, an addressable system should be used. The final decision is based on the fire protection design documentation.

Can devices from different manufacturers be used together? 

Only when the manufacturer confirms compatibility. TCVN 5738:2021 requires the fire alarm center to be compatible with the detectors; with the address system, the communication protocol is usually specific to the manufacturer.

Does the EN 54 standard replace TCVN? 

No. EN 54 is a certification of the equipment; design and installation in Vietnam must still meet Vietnamese standards and regulations.

Finder fire alarm system solutions from Handyman

DLV Corporation (Handyman) is the authorized installer for the Finder fire alarm system, providing, installing, and maintaining the Finder fire alarm system in Vietnam. Finder has the conventional fire alarm line 100 Series and the addressable fire alarm lines 200, 500, 700 Series, along with wireless and marine lines.

Handyman provides genuine products with commercial contracts, valid VAT invoices, and documents as required by the industry, technical support to choose the right equipment, and receive multiple item codes in one order.

Send a request for a survey and quotation for the Finder fire alarm system at the fire alarm equipment page or call the hotline 0988.678.120.


What is the role of the main power source and backup power source of the fire alarm panel?