What is the role of the main power source and backup power source of the fire alarm panel?

November 15, 2026 by
What is the role of the main power source and backup power source of the fire alarm panel?
CÔNG TY CỔ PHẦN ĐẦU TƯ THƯƠNG MẠI DỊCH VỤ VÀ TƯ VẤN ĐỖ LÊ VŨ, Marketing Team - SAMASER Holdings

Fires often accompany electrical incidents, and that is when the fire alarm system needs to operate the most. Therefore, the backup power source for the fire alarm panel is a mandatory requirement, not an optional accessory. This article explains the role of the main power source, backup power source, requirements according to TCVN 5738:2021, and how to calculate battery capacity.

What power sources does the fire alarm panel need?

The fire alarm panel must have two independent power sources: one 220 V AC mains power as the main source and one backup battery source. This is a requirement under Article 10.1 of TCVN 5738:2021. The European standard EN 54-4 for power supply equipment also requires at least two sources: the main source and the backup source.

Source

Role

Main requirement

Main source (mains power)

Power the panel and devices under normal conditions, while also charging the battery

220 V AC, fluctuating no more than ±10%; exceeding this must use a voltage stabilizer

Backup source (battery)

Automatically takes over when mains power is lost

Sufficient for at least 24 hours of standby and 1 hour during a fire; automatically charged

In addition, the fire alarm center must be grounded for protection according to Article 10.2 of the standard.

What is the role of the main source of the fire alarm panel?

The main source supplies power to the panel, detectors, modules, and warning devices under normal conditions, while keeping the battery fully charged. The power supply in the panel converts AC mains power to DC power, typically 24 V DC, to power the signal circuit and outputs.

For example with Finder devices:

  • Conventional fire alarm panel FF-CF104 / FF-CF108: input power 230 V AC, output 24 V DC 0.5 A, with smart battery charging function to extend battery life.

  • Addressable fire alarm panel FF-SYN2L: input power 230 V AC, power supply 4 A according to EN 54-4.

When the load of the siren, lights, and interlocking devices exceeds the capacity of the power supply in the panel, an additional fire alarm power supply is needed. For example, Finder FF-PSU2405: input power 240 V AC 50–60 Hz, output 20–24 V DC ±2%, output current 1 × 5 A or 2 × 2.5 A, smart battery charging with temperature compensation, short circuit and overload protection, dry contact relay for fault indication, compliant with EN 54-4.

What is the role of the backup power source for the fire alarm panel?

The backup power source keeps the system operational during a power outage, including when a fire damages the electrical circuit or when the operator cuts power to the fire area. According to TCVN 5738:2021, the capacity of the backup battery must be sufficient for at least 24 hours in standby mode and 1 hour during a fire.

  • 24 hours standby: the panel continues to monitor the detectors and circuits while waiting for power restoration.

  • 1 hour fire alarm: enough energy to power the bell, siren, lights, and interlocking devices at the highest consumption level.

  • Automatic charging: the battery must be automatically charged by the panel to always be ready.

The Finder FF-CF104 / FF-CF108 panel uses a 12 V 7 Ah lead-acid battery as a backup power source. The FF-PSU2405 auxiliary power supply uses 2 12 V 7 Ah batteries.

How to calculate the battery capacity for the fire alarm panel?

The minimum battery capacity equals the standby current multiplied by 24 hours, plus the fire alarm current multiplied by 1 hour. Then add the safety factor according to the manufacturer's recommendations or design consultant, and then select a battery with the nearest higher standard capacity.

Steps to perform:

  1. Add the standby current of the panel and all devices on the circuit (according to the datasheet of each device).

  2. Add the current during a fire alarm: panel, siren, lights, interlocking module in the activated state.

  3. Apply the above formula and add the safety factor.

  4. Compare with the maximum battery capacity that the panel or power supply allows; if exceeded, an additional auxiliary power supply is needed.

Illustrative example (assumed numbers): standby current 0.15 A and fire alarm current 0.8 A gives C = 0.15 × 24 + 0.8 × 1 = 4.4 Ah, not including the safety factor.

When should the fire alarm panel battery be checked or replaced?

A weak battery is a common reason for the panel to report a power fault or insufficient operating time during a power outage. It is advisable to check the backup power during each scheduled maintenance and replace the battery according to the manufacturer's recommendations.

  • Power fault panel, battery fault, or charger fault.

  • Swollen battery, leakage, oxidized terminals.

  • Try cutting off the mains power while the panel does not switch to battery or shuts down quickly.

  • After adding horns, lights, modules to the installation: recalculate the battery capacity.

When replacing, use the correct voltage, capacity, and type of battery according to the panel's documentation.

Frequently Asked Questions

Can a UPS be used instead of the battery for the fire alarm panel? TCVN 5738:2021 specifies that the backup power is a battery that is automatically charged. Other options need to be considered by the fire protection design unit according to the project documentation.

Why does the new battery still show a power fault on the panel? Usually due to incorrect connections, insufficient charging, using the wrong capacity, or a faulty charger. It is necessary to check according to the manufacturer's instructions.

When is a supplementary power supply needed for fire alarms? When the total current of the horns, lights, and interlocking devices exceeds the power supply capacity in the panel, or when devices are placed far from the panel causing voltage drop on the wires. It is advisable to choose a supplementary power supply that meets EN 54-4.

Power and battery for the Finder fire alarm panel at Handyman

Handyman provides the Finder fire alarm panel, Finder FF-PSU2405 supplementary power supply, and suitable batteries according to the panel's documentation. DLV Corporation (Handyman) is the authorized installer for the Finder fire alarm system, supporting load calculations, battery capacity calculations, and regular maintenance.

Request a quote for the supplementary power supply and battery from the battery catalog for the fire alarm panel or call the hotline 0988.678.120.