Understanding the structure and principles of the fire alarm system helps the technical department read the design documents correctly, respond appropriately when the alarm panel indicates an error, and select the right equipment when expanding or replacing. The article describes each component and how they work together from the moment a fire is detected until the alert is issued.
What does the fire alarm system consist of?
The fire alarm system consists of 5 parts: the fire alarm control panel, smoke detectors, manual pull stations, interconnecting devices, and the power supply. They can be categorized by function: input devices that detect fire, processing center, output devices that alert and interconnect, along with the power supply for the entire system.
Group | Component | Function |
Input | Smoke, heat, fire detectors, beam smoke detectors; manual fire alarm button; input module | Automatically detect fire or receive signals from people, from other devices |
Processing | Fire alarm center (fire alarm panel) | Receive, check signals, display location, issue alerts and interlock |
Output | Bell, siren, flashing light; output module, relay | Issue alerts, control peripheral devices |
Link | Signal cable, junction box, isolation module | Transmit signals, zone the line fault |
Power | Mains power, power supply, backup battery | Power the system even during power outages |
How do fire detectors and manual fire alarm buttons work?
Fire detectors continuously measure a sign of fire and send a signal to the panel when thresholds are exceeded. The manual fire alarm button is a device for a person to manually alert to a fire, usually placed in hallways, stairways, and escape routes. These two types complement each other.
Smoke detector: detects smoke during smoldering stages, used for offices, hallways, technical rooms.
Heat detector: reacts to temperature, used in places with dust, steam, or household smoke that may cause false alarms in smoke detectors.
Combined smoke – heat detector: decides to alarm from one or both sensors.
Flame detector: recognizes radiation from flames, used in areas containing fuel, flammable liquids.
Beam smoke detector: uses a beam to scan large spaces such as warehouses, high-ceiling workshops.
What role does the fire alarm center play in the system?
The fire alarm center is the brain of the system. According to TCVN 5738:2021, this is the device that supplies power to the detectors and other devices, receives signals, triggers alarms, indicates fire locations, monitors faults such as wire breaks, short circuits, and controls peripheral devices.
The standard also requires that the fire alarm signal and the fault signal on the panel must be different, so that the operator can immediately distinguish whether there is a fire or the system is faulty. Details of each function can be found in the article [what functions does the fire alarm center have](need URL article 3).
How does the fire alarm system operate?
The operating principle consists of three sequential stages: detection, processing, and warning. Normally, the system is in standby mode, continuously monitoring the detectors and the wiring. When there is a fire, the signal goes from the detector or the push button to the panel, which determines the location and activates the alarm.
Standby: the panel supplies power and monitors the entire signal circuit. TCVN 5738:2021 requires the signal circuit to be automatically tested along its entire length.
Detection: the detector exceeds the threshold or a person presses the fire alarm button.
Processing: the panel checks the signal to eliminate false alarms, then determines the zone or alarm address.
Warning: the panel displays the location, activates bells, sirens, lights, and sends signals to where the operator is.
Interlocking: the panel controls the fire extinguishing system, smoke exhaust fans, elevators, and cuts power as programmed.
Restoration: after processing, the authorized person confirms and returns the system to standby.
For the automatic fire extinguishing system controlled by the fire alarm system, TCVN 5738:2021 requires each point to be monitored by 2 detectors belonging to 2 different channels or addresses.
How do the power supply and wiring affect the operating principle?
The system only works correctly when the power source and wiring are stable. TCVN 5738:2021 requires two independent sources (mains power and battery), the resistance of the wiring for each channel must not exceed 100 Ω, and a 20% reserve for connectors in the junction box as well as the core of the main cable.
The wiring method according to zone or loop determines how detailed the alarm panel's location is: see [zone and loop in the fire alarm system](need URL article 4).
The backup power source determines how long the system will continue to operate during a power outage: see [main power and backup power of the fire alarm panel](need URL article 5).
Frequently Asked Questions
Why doesn't the fire alarm panel alert immediately when the detector is triggered?
Many panels have a signal verification step to eliminate false alarms, in accordance with the signal testing requirements of TCVN 5738:2021. The verification time is set according to the manufacturer's documentation.
What is the difference between a "fault" alarm panel and a "fire" alarm panel?
A fault alarm indicates that there is an issue with the system such as a broken wire, short circuit, or power loss; a fire alarm indicates signs of fire. These two signals must differ in sound and light.
Is it necessary to have both automatic detectors and manual fire alarm buttons?
Yes. The detectors automatically detect, while the manual button allows someone who sees a fire to alert immediately. The location and quantity are according to the fire protection design documents.
Finder fire alarm system equipment at Handyman
Finder provides all components of the system: conventional and addressable fire alarm panels, smoke detectors, heat detectors, smoke-heat detectors, manual buttons, sounder lights, input/output modules, isolation modules, and external power supplies. DLV Corporation (Handyman) is the authorized installer for the Finder fire alarm system, providing, installing, and maintaining the entire system.